| Datasheet | Download |
| Installation Manual | Download |
| INMETRO Installation Manual | Download |
| IECEx certificate | Download |
| ATEX certificate | Download |
| UKCA Certificate | Download |
| EC CPR Certificate | Download |
| INMETRO certificate | Download |
| Ex EAC TR CU 012/2011 Certificate | Download |
| CCOE PESO | Download |
| ECAS Ex Approval | Download |
| Hong Kong Fire Dept. cert. | Download |
| Declaration of Conformity | Download |
| Declaration of Conformity SIL2 | Download |
| SIL1 Certificate | Download |
| Declaration of Conformity UKCA | Download |
| Declaration of Performance | Download |
| 2D drawing (PDF) | Download |
| 2D drawing (DWG) | Download |
| 3D drawing (STEP) | Download |
| EOL Monitoring Drawing | Download |
| Wiring Schematic DC voltage | Download |
| Wiring Schematic AC voltage | Download |
| Nameplate Drawing | Download |
| Equipment Tag Drawing | Download |
| Duty Label Drawing | Download |
| Pole Mount & Sun Shade Drawing | Download |
| Hi-res product image 1 (TIFF) | Download |
| Hi-res product image 2 (TIFF) | Download |
| Maximum output: | 123dB(A) @ 1 metre [114dB(A) @ 10ft/3m] |
| Nominal output: | 117dB(A) @ 1m +/- 3dB – Tone 2 [108dB(A) @ 10ft/3m] |
| No. of tones: | 32 (UKOOA / PFEER compliant) |
| No. of stages: | 3 |
| Volume control: | Max. 117dB(A); Min. 108dB(A) – Tone 2 |
| Effective range: | 200m/656ft @ 1KHz |
| Voltages DC: | 12Vdc; 24Vdc; 48Vdc |
| Voltages AC: | 115Vac; 230Vac |
| Stage switching: | Negative or positive |
| Ingress protection: | IP66/67 |
| Enclosure matl: | Marine grade copper free LM6 Aluminium |
| Enclosure finish: | Chromate & powder coated finish ISO 12944-6 CX, C5VH & C5H |
| Colour: | Red or Special – available on request |
| BExS120 horn: | High impact UL94 V0 & 5VA FR ABS |
| Cable entries: | Dual M20 ISO (one stopping plug inc) |
| Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
| Line monitoring: | Min. 500 Ohm 2w, or 3k3 Ohm 0.5w res. or diode within Exd enclosure (dc versions) |
| Relative humidity: | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
| MTBF DC: | 173.75 years / 1,522,071 hours – MIL 217 |
| MTBF AC: | 170.13 years / 1,490,212 hours – MIL 217 |
| Weight: | DC: 3.20kg/7.04Ibs AC: 3.40kg/7.48Ibs |
| Version A1: | SIL1 and SIL2 Route 2H |
| Version P1: | Stage programmable – 4 remotely selectable stages 45 alarm tones – any tone can be assigned to any stage. User configurable continuous frequency tone SIL1 and SIL2 Route 2H |
| Version T1: | Tropicalised SIL1 and SIL2 Route 2H |
| Note | *SPL data +/-3dB(A). Measured at optimum voltage. |
| Part Code: | Identifier: | Description: | |
|---|---|---|---|
| Product type: | BExS120 | Explosion proof alarm horn sounder | |
| Type: | DF | Ex d, Flare re-entrant horn | |
| Voltage: | DC012 DC024 DC048 AC115 AC230 | 12V dc 24V dc 48V dc 115V ac 240V ac | |
| Cable entries:[e] | A B C D E F G | 2 x M20x1.5mm 2 × 1/2" NPT – adaptors 2 × 3/4" NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 1/2" NPT – adaptor 1 × 3/4" NPT – adaptor 1 x M25x1.5mm – adaptor | |
| Stopping plug/adaptor material: [m] | B N S | Brass Nickel Plated Stainless Steel | |
| Bracket matl & tag: [s] | 1 2 3 4 | A2 304 Stainless Steel A4 316 Stainless Steel A2 304 St/St with Equip. Tag A4 316 St/St with Equip. Tag | |
| Product version: [v] | A1 P1 T1 | Default – IECEx, ATEX, Ex EAC & INMETRO– SIL1 & SIL2 Stage programmable – IECEx, ATEX, Ex EAC & INMETRO – SIL1 & SIL2 Tropicalised – IECEx, ATEX, Ex EAC & INMETRO – SIL1 & SIL2 | |
| Enclosure colour: [x] | R S | Red Special – contact E2S | |
| Accessories | |||
| SP65-0001-A4 | |||
| SP65-0003-A4 | |||
| Version: | Voltage: | Current: |
|---|---|---|
| 12V dc | +/-25% | 850mA |
| 24V dc | +/-25% | 800mA |
| 48V dc | +/-25% | 420mA |
| 115V ac 50/60Hz | +10/-10% | 180mA |
| 230V ac 50/60Hz | +10/-10% | 90mA |
| Stage 1 | WAV file | Frequency Description. | Stage 2 | Stage 3 |
|---|---|---|---|---|
| T 1 | Continuous 1000Hz Toxic Gas Alarm | T 31 | T 11 | |
| T 2 | Alternating 800/1000Hz at 0.25s intervals | T 17 | T 5 | |
| T 3 | Slow Whoop 500/1200Hz at 0.3Hz with 0.5s gap repeated | T 2 | T 5 | |
| T 4 | Sweeping 800/1000 at 1Hz | T 6 | T 5 | |
| T 5 | Continuous at 2400Hz | T 3 | T 27 | |
| T 6 | Sweeping 2400/2900Hz at 7Hz | T 7 | T 5 | |
| T 7 | Sweeping 2400/2900Hz at 1Hz | T 10 | T 5 | |
| T 8 | Siren 500/1200/500Hz at 0.3Hz | T 2 | T 5 | |
| T 9 | Sawtooth 1200/500Hz at 1Hz | T 15 | T 2 | |
| T 10 | Alternating 2400/2900Hz at 2Hz | T 7 | T 5 | |
| T 11 | Intermittent 1000Hz at 0.5Hz General alarm | T 31 | T 1 | |
| T 12 | Alternating 800/1000Hz at 0.875Hz | T 4 | T 5 | |
| T 13 | Intermittent 2400Hz at 1Hz | T 15 | T 5 | |
| T 14 | Intermittent 800Hz 0.25s on 1s off | T 4 | T 5 | |
| T 15 | Continuous at 800Hz | T 2 | T 5 | |
| T 16 | Intermittent 660Hz 150mS on, 150mS off | T 18 | T 5 | |
| T 17 | Alternating 544Hz (100mS)/440Hz(400mS) | T 2 | T 27 | |
| T 18 | Intermittent 660Hz 1.8s on, 1.8s off | T 2 | T 5 | |
| T 19 | 1400Hz to 1600Hz sweep up over 1s -1600Hz to 1400Hz sweep down over 0.5s | T 2 | T 5 | |
| T 20 | Continuous 660Hz | T 2 | T 5 | |
| T 21 | Alternating 554/440Hz at 1Hz | T 2 | T 5 | |
| T 22 | Intermittent 554Hz at 0.875Hz | T 2 | T 5 | |
| T 23 | 800Hz pulsing at 2Hz | T 6 | T 5 | |
| T 24 | Sweeping 800/1000Hz at 50Hz | T 29 | T 5 | |
| T 25 | Sweeping 2400/2900Hz at 50Hz | T 29 | T 5 | |
| T 26 | Simulated bell sound | T 2 | T 1 | |
| T 27 | Continuous 554Hz | T 26 | T 5 | |
| T 28 | Continuous 440Hz | T 2 | T 5 | |
| T 29 | Sweeping 800/1000Hz at 7Hz | T 7 | T 5 | |
| T 30 | 420Hz repeating 0.625s on, 0.625s off Australian alert signal | T 32 | T 5 | |
| T 31 | 1200/500Hz at 1 Hz Prepare to Abandon Platform | T 11 | T 1 | |
| T 32 | Sweeping 500/1200Hz 3.75s on, 0.25s off 15Hz | T 26 | T 1 |