| Datasheet | Download |
| Installation Manual | Download |
| IECEx certificate | Download |
| ATEX certificate | Download |
| UL certificate of compliance | Download |
| UKCA Certificate | Download |
| CSFM Listing | Download |
| DNV Type Approval | Download |
| ECAS Ex Approval | Download |
| Declaration of Conformity | Download |
| Declaration of Conformity UKCA | Download |
| 2D drawing (PDF) | Download |
| 2D drawing (DWG) | Download |
| 3D drawing (STEP) | Download |
| Wiring Schematic DC voltage | Download |
| Wiring Schematic AC voltage | Download |
| Nameplate Drawing | Download |
| Nameplate Drawing | Download |
| Equipment Tag Drawing | Download |
| Duty Label Drawing | Download |
| Pole Mount & Sun Shade Drawing | Download |
| Maximum output: | High power level: 129dB(A) @ 1 m +/- 3dB [120dB(A) @ 10ft/3m +/- 3dB] Medium power level: 126dB(A) @ 1 m +/- 3dB [117dB(A) @ 10ft/3m +/- 3dB] |
| Nominal output: | High power level: 127dB(A) @ 1m +/- 3dB [116dB(A) @ 10ft/3m] +/- 3dB Medium power level: 123dB(A) @ 1m +/- 3dB [114dB(A) @ 10ft/3m] +/- 3dB |
| No. of tones: | 64 (UKOOA / PFEER compliant) |
| No. of stages: | 4 |
| Volume control: | Full range |
| Effective range: | >350m/1148ft @ 1KHz |
| Voltages DC: | 24Vdc (11.5-54Vdc) |
| Voltages AC: | 230Vac (100-240Vac) |
| In-rush: | 815mA within 4ms @ 24Vdc |
| Stage switching: | DC units: positive or negative AC units: common supply line |
| Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
| Ingress protection: | EN60529: IP66/67 UL50E / NEMA250: 4 / 4X / 3R / 13 |
| Enclosure material: | Marine grade LM6 aluminium alloy |
| Enclosure finish: | Chromate & powder coated finish ISO 12944-6 CX, C5VH & C5H |
| Enclosure colour: | Red or Grey, custom colours available on request |
| Cable entries: | 1×1/2"NPT & 2xM20 Thread adaptors available |
| Stopping plugs: | Brass, Nickel Plated or Stainless Steel |
| Terminals: | 0.5 – 2.5mm² (20-14AWG) – 12AWG solid core conductor Pluggable & duplicated terminals |
| Line monitoring: | Blocking diode included 24Vdc: EOL Min. 1K Ohm 2W, or 3K9 Ohm 0.5W resistor 24Vdc: EOL Min. 3K9 Ohm 2W, or 15K Ohm 0.5W resistor or diode (DC versions) can be fitted |
| Ground/Earth stud: | M5 |
| Enclosure volume: | <2 litres |
| Installation temp: | -55 to +85°C [-67° to +185°F] |
| Storage temp: | -55 to +85°C [-67° to +185°F] |
| Relative humidity: | 99% – tropicalised/conformal coated electronics |
| Vibration test: | 35Hz for a duration 4Hr (UL464) |
| Jarring test: | 3ft/lb Energy (UL464) |
| Impact test: | 3x 5lb (UL464) |
| MTBF DC: | 225.16 years / 1,972,386 hours – MIL 217 |
| MTBF AC: | 138.96 years / 1,217,285 hours – MIL 217 |
| Weight: | 4.6kg/10.1lbs |
| Part Code: | Identifier: | Description: | |
|---|---|---|---|
| Product type: | D2xS2 | D2xS2 alarm horn sounder | |
| Horn type: | H | High SPL flare re-entrant horn | |
| Voltage: | DC024 AC230 | 11.5-54Vdc 100-240Vac | |
| Cable entries:[e] | A B C D F G Note: | 2 x M20x1.5mm & 1 × 1/2"NPT 2 × 1/2"NPT – adaptors 2 × 3/4"NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 3/4"NPT – adaptor 1 x M25x1.5mm – adaptor All entries, excluding thread adaptors, supplied with stopping plugs installed. | |
| Stopping plug/adaptor material: [m] | B N S | Brass Nickel plated brass Stainless steel | |
| Bracket material: [s] | 1 3 5 | A4 316 Stainless Steel A4 316 St/St with Equip. Tag A4 316 St/St with Equip. Tag and Duty Label | |
| Product version:[v] | A | UL, cUL, ULC, IECEx, ATEX, DNV – SIL1 & SIL2 Route 2H | |
| Product option:[o] | 1 Z X Y K V | Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 Stage control Config. 5 (DC) and Config. 2 (AC) Stage control Config. 6 | |
| Enclosure colour: [x] | R G S | Red Grey Special colour – contact E2S | |
| Accessories | |||
| SP65-0001-A4 | |||
| Config. 1 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | ||
| Config. 2 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | ||
| Config. 3 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | ||
| Config. 4 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | ||
| Config. 5 [DC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages | ||
| Config. 6 [DC]: | Product option ‘V’. Independent activation of up to 4 Alarm Stages with EOL on all stages. Forward polarity monitoring | ||
| Config. 1 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts | ||
| Config. 2 [AC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages | ||
| NominalVoltage: | Voltagerange: | Default Power Nom.current: | Default Power Max.Current: | High Power Nom.current: | High Power Max.Current: | In-rush: |
|---|---|---|---|---|---|---|
| 12Vdc | 11.5-54Vdc | 289mA | 324mA | 356mA | 740mA | 815mA <4ms |
| 24Vdc | 11.5-54Vdc | 324mA | 324mA | 740mA | 740mA | 815mA <4ms |
| 48Vdc | 11.5-54Vdc | 195mA | 324mA | 391mA | 740mA | 815mA <4ms |
| 115Vac 50/60Hz | 100-240V ac | 125mA | 138mA | 282mA | 325mA | - |
| 230Vac 50/60Hz | 100-240V ac | 78mA | 138mA | 167mA | 325mA | - |
| Stage 1 | WAV file | Frequency Description. | Stage 2 | Stage 3 |
|---|---|---|---|---|
| T 1 | 1000 Continuous – PFEER Toxic Gas | Any | T 2 | |
| T 2 | 1200/500 @ 1Hz Sweeping – DIN / PFEER P.T.A.P. | Any | T 3 | |
| T 3 | 1000 @ 0.5Hz (1s on, 1s off) Intermittent – PFEER Gen. Alarm | Any | T 2 | |
| T 4 | 1.4KH-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s – NF C 48-265 | Any | T 24 | |
| T 5 | 544(100mS)/440 (400mS) – NF S 32-001 | Any | T 19 | |
| T 6 | 1500/500 – (0.5s on , 0.5s off) x3 + 1s gap – AS4428 | Any | T 44 | |
| T 7 | 500-1500Hz Sweeping 2 sec on 1 sec off – AS4428 | Any | T 44 | |
| T 8 | 500/1200Hz @ 0.26Hz(3.3s on, 0.5s off) – NEN 2575 | Any | T 24 | |
| T 9 | 1000 (1s on, 1s off)x7 + (7s on, 1s off) – IMO Code 1a | Any | T 34 | |
| T 10 | 1000 (1s on, 1s off)x7 + (7s on, 1s off) – IMO Code 1a | Any | T 34 | |
| T 11 | 420(0.5s on, 0.5s off)x3 + 1s gap – ISO 8201 Temporal | Any | T 1 | |
| T 12 | 1000(0.5s on, 0.5s off)x3 + 1s gap – ISO 8201 Temporal | Any | T 1 | |
| T 13 | 422/775 – (0.85 on, 0.5 off) x3 + 1s gap – NFPA Temporal | Any | T 1 | |
| T 14 | 1000/2000 @ 1Hz – Singapore | Any | T 3 | |
| T 15 | 300 Continuous | Any | T 24 | |
| T 16 | 440 Continuous | Any | T 24 | |
| T 17 | 470 Continuous | Any | T 24 | |
| T 18 | 500 Continuous – IMO code 2 (Low) | Any | T 24 | |
| T 19 | 554 Continuous | Any | T 24 | |
| T 20 | 660 Continuous | Any | T 24 | |
| T 21 | 800 Continuous – IMO code 2 (High) | Any | T 24 | |
| T 22 | 1200 Continuous | Any | T 24 | |
| T 23 | 2000 Continuous | Any | T 3 | |
| T 24 | 2400 Continuous | Any | T 20 | |
| T 25 | 440 @ 0.83Hz (0.60s on, 0.60s off) Intermittent | Any | T 44 | |
| T 26 | 470 @ 0.9Hz (0.55s on, 0.55s off) Intermittent | Any | T 44 | |
| T 27 | 470 @ 5Hz (0.10s on, 0.10s off) Intermittent | Any | T 44 | |
| T 28 | 544 @ 1.14Hz (0.43s on, 0.44s off) Intermittent | Any | T 24 | |
| T 29 | 655 @ 0.875Hz (0.57s on, 0.57s off) Intermittent | Any | T 44 | |
| T 30 | 660 @ 0.28Hz (1.80s on, 1.80s off) Intermittent | Any | T 24 | |
| T 31 | 660 @ 3.3Hz (0.15s on, 0.15s off) Intermittent | Any | T 24 | |
| T 32 | 745 @ 1Hz (0.50s on, 0.50s off) Intermittent | Any | T 24 | |
| T 33 | 800 (0.25s on, 1.00s off) Intermittent | Any | T 24 | |
| T 34 | 800 @ 2Hz (0.25s on, 0.25s off) – IMO code 3.a (High) | Any | T 24 | |
| T 35 | 1000 @ 1Hz (0.50s on, 0.50s off) Intermittent | Any | T 24 | |
| T 36 | 2400 @ 1Hz (0.50s on, 0.50s off) Intermittent | Any | T 24 | |
| T 37 | 2900 @ 5Hz (0.10s on, 0.10s off) Intermittent | Any | T 24 | |
| T 38 | 363/518 @ 1Hz (0.50s / 0.50s) Alternating | Any | T 8 | |
| T 39 | 450/500 @ 2Hz (0.25s / 0.25s) Alternating | Any | T 8 | |
| T 40 | 554/440 @ 1Hz (0.50s / 0.50s) Alternating | Any | T 24 | |
| T 41 | 554/440 @ 0.65Hz (0.76s / 0.76s) Alternating | Any | T 8 | |
| T 42 | 561/760 @ 0.83Hz (0.60s / 0.60s) Alternating | Any | T 8 | |
| T 43 | 780/600 @ 0.96Hz (0.52s / 0.52s) Alternating | Any | T 8 | |
| T 44 | 800/1000 @ 2Hz (0.25s / 0.25s) Alternating | Any | T 24 | |
| T 45 | 970/800 @ 2Hz (0.25s / 0.25s) Alternating | Any | T 8 | |
| T 46 | 800/1000 @ 0.875Hz (0.57s / 0.57s) Alternating | Any | T 24 | |
| T 47 | 2400/2900 @ 2Hz (0.25s / 0.25s) Alternating | Any | T 24 | |
| T 48 | 500/1200 @ 0.3Hz (1.67s / 1.67s) Sweeping | Any | T 24 | |
| T 49 | 560/1055 @ 0.18Hz (2.73s / 2.73s) Sweeping | Any | T 24 | |
| T 50 | 560/1055 @ 3.3Hz (0.15s / 0.15s) Sweeping | Any | T 24 | |
| T 51 | 600/1250 @ 0.125Hz (4s / 4s) Sweeping | Any | T 24 | |
| T 52 | 660/1200 @ 1Hz (0.50s / 0.50s) Sweeping | Any | T 24 | |
| T 53 | 800/1000 @ 1Hz (0.50s / 0.50s) Sweeping | Any | T 24 | |
| T 54 | 800/1000 @ 7Hz (0.07s / 0.07s) Sweeping | Any | T 24 | |
| T 55 | 800/1000 @ 50Hz (0.01s / 0.01s) Sweeping | Any | T 24 | |
| T 56 | 2400/2900 @ 7Hz (0.07s / 0.07s) Sweeping | Any | T 24 | |
| T 57 | 2400/2900 @ 1Hz (0.50s / 0.50s) Sweeping | Any | T 24 | |
| T 58 | 2400/2900 @ 50Hz (0.01s / 0.01s) Sweeping | Any | T 24 | |
| T 59 | 2500/3000 @ 2Hz (0.25s / 0.25s) Sweeping | Any | T 24 | |
| T 60 | 2500/3000 @ 7.7Hz (0.65s / 0.65s) Sweeping | Any | T 24 | |
| T 61 | 800Hz Motor Siren | Any | T 24 | |
| T 62 | 1200Hz Motor Siren | Any | T 24 | |
| T 63 | 2400Hz Motor Siren | Any | T 24 | |
| T 64 | Simulated Bell | Any | T 21 |