E2xS1F Alarm Sounder/Horn Alarm Horn 116dB(A)

Features and Functions

  • Automatic synchronisation on multi-sounder system.
  • Continuously rated.
  • Large termination area.
  • Stainless steel fixings.
  • Ratchet adjustable stainless steel ‘U’ bracket for 360° positioning.
  • Duplicate cable terminations (in & out for daisy-chain installations).
  • Tropicalisation available on request.
  • Available with custom tone configurations and frequencies.
Ul badge certified
Ul
Iecex approval
Atex approval
Ex eac logo
Eac logo
Ce approval
Ukca
Culs approval

Overview

With a nominal sound level output of 116dB(A) at 1 metre and a choice of 45 alarm tones and 3 remotely selectable stages the E2xS1F alarm sounder horn is suitable for all general signalling duties.
The E2x range features enclosures manufactured from lightweight, corrosion proof GRP and high impact, fire retardant ABS re-entrant flare horns; both of which are suitable for the harshest of environments.

Downloads
Datasheet Download
Installation Manual Download
IECEx certificate Download
ATEX certificate Download
UL certificate of compliance Download
UKCA Certificate Download
Declaration of Conformity Download
Declaration of Conformity UKCA Download
2D drawing (PDF) Download
2D drawing (DWG) Download
3D drawing (STEP) Download
Wiring Schematic Download
Nameplate Drawing Download
Duty Label Drawing Download
Equipment Tag Drawing Download
Hi-res product image 1 (TIFF) Download
Specification
Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output: 113dB(A) @ 1m +/- 3dB – Tone 2 [104dB(A) @ 10ft/3m]
No. of tones: 45 (UKOOA/PFEER compliant)
No. of stages: 3
Volume control: Max. 113dB(A); Min. 105dB(A)
- Tone 2
Effective range: 100m/328ft @ 1KHz
Voltages DC: 24Vdc (10-30Vdc); 48Vdc
Voltages AC: 115Vac; 230Vac
Ingress protection: IP rating per EN60079-0:IP64
IP rating per EN60529:IP66
Type rating per UL50E/NEMA250:4/4X/13
Enclosure material: UL94V0 GRP (PPS) & ABS
Cable entries: Dual M20x1.5 or 1/2"NPT
Terminals: 0.5 – 2.5mm² (20-14 AWG)
Line monitoring: Blocking diode included
EOL can be factory fitted
Operating temp: -20 to +55°C [-4° to +131°F]
Storage temp: -40 to +70°C [-40° to +158°F]
Relative humidity: 90% at 20°C [68°F]
Weight: DC: 2.5kg/5.5Ibs AC: 3.00kg/6.6Ibs
Note *SPL data +/-3dB(A). Measured at optimum voltage.
Part codes
Part Code:Identifier:Description:
Product type:E2xS1E2xS1 alarm horn sounder
Flare type:FFlare Horn
Voltage:AC115
AC230
DC024
DC048
115V ac 50/60Hz
230V ac 50/60Hz
24V dc (10-30V dc)
48V dc
Cable entries:A
B
C
M20x1.5 & ½” NPT
M20x1.5 & M20x1.5
½” NPT & ½” NPT
Stopping plug material:NNylon
Bracket & tag: [s]1
2
3
4
304 A2 Stainless Steel
316 A4 Stainless Steel
304 A2 Stainless Steel & Equip. Tag
316 A4 Stainless Steel & Equip. Tag
Approvals:A1UL, cULs, IECEx & ATEX
Enclosure:BBlack
Accessories:SP65-0001-A4
SP65-0003-A4
Pole Mount Bracket Kit St/St A4 (316)
Sunshade – St/St A4 (316)
Current Consumption
Version:Voltage:Current:
24V dc10-30vdc284mA
48V dc38-58vdc146mA
115V ac 50/60Hz+/-10%104mA
230V ac 50/60Hz+/-10%54mA
Approvals
  • ATEX certificate: DEMKO 06 ATEX 0421554X
  • IECEx certificate: IECEx ULD 14.0012X
  • UL/cUL File ref: E230764
  • UKCA certificate: UL21UKEX2135X
  • Ex EAC certified: EAC RU C-GB.AA71.B.00273/20
Coding
  • IECEx / ATEX:
    II 3G Ex ec IIC T4 Gc Ta -20°C to +55°C
    II 3D Ex tc IIIC T85°C Dc Ta -20°C to +55°C
  • NEC Class / Zone ratings US:
    Class I Zone 2 AEx ec IIC T4 Gc Ta -20°C to +55°C
    Zone 22 AEx tc IIIB T85°C Dc Ta -20°C to +55°C
  • CEC Class / Zone ratings Canada
    Class I Zone 2 Ex ec IIC T4 Gc X Ta -20°C to +55°C
    Zone 22 Ex tc IIIC T85°C Dc Ta -20°C to +55°C
  • NEC & CEC Class / Division Ratings for US / Canada
    Class I Div 2 Group ABCD T3C Ta -20°C to +55°C
    Class I Div 2 Group ABCD T4 Ta -20°C to +40°C
    Class II Div 2 Group FG T6 Ta -20°C to +55°C
    Class III Div 1 & 2 Ta -20°C to +55°C
Tone Table
Stage 1 WAV file Frequency Description. Stage 2 Stage 3
T 1 T 2 T 5
T 2 T 17 T 5
T 3 T 2 T 5
T 4 T 6 T 5
T 5 T 3 T 20
T 6 T 7 T 5
T 7 T 10 T 5
T 8 T 2 T 5
T 9 T 15 T 2
T 10 T 7 T 5
T 11 T 2 T 5
T 12 T 4 T 5
T 13 T 15 T 5
T 14 T 4 T 5
T 15 T 2 T 5
T 16 T 18 T 5
T 17 T 2 T 27
T 18 T 2 T 5
T 19 T 2 T 5
T 20 T 2 T 5
T 21 T 2 T 5
T 22 T 2 T 5
T 23 T 6 T 5
T 24 T 29 T 5
T 25 T 29 T 5
T 26 T 2 T 15
T 27 T 26 T 5
T 28 T 2 T 5
T 29 T 7 T 5
T 30 T 2 T 5
T 31 T 26 T 5
T 32 T 26 T 15
T 33 T 2 T 5
T 34 T 38 T 45
T 35 T 36 T 5
T 36 T 35 T 5
T 37 T 9 T 45
T 38 T 34 T 45
T 39 T 23 T 17
T 40 T 31 T 27
T 41 T 2 T 5
T 42 T 2 T 5
T 43 T 2 T 5
T 44 T 2 T 5
T 45 T 38 T 34

Настройки файлов cookie

Мы используем файлы cookie, чтобы обеспечить вам удобство прохождения собеседований, улучшить наш продукт, персонализировать ваш опыт и поддержать наши маркетинговые усилия. Полный список файлов cookie, используемых по категориям, приведен ниже. Вы можете отказаться/отключиться в любое время. Для получения более подробной информации ознакомьтесь с нашей полной политикой конфиденциальности.

Строго необходимые файлы cookie
Эти файлы cookie необходимы для работы нашего веб-сайта и не могут быть отключены. К ним относятся файлы cookie, используемые для аутентификации и статуса, безопасности, персонализации и функций корзины покупок.
Файлы cookie производительности и аналитики
Эти файлы cookie позволяют нам измерять посещаемость веб-сайта и источники трафика. Мы используем их для определения популярных страниц и оптимизации работы сайта.
Целевые файлы cookie
Эти файлы cookie позволяют нам измерять эффективность нашей маркетинговой программы и устанавливаются нашими рекламными партнерами. Их можно использовать для создания профиля ваших интересов и для показа соответствующей рекламы на других веб-сайтах.

Получить типовой расчет

Предоставьте свои контактные данные, и мы скоро свяжемся с вами!
В этой форме указывается ваше имя и контактная информация. Пожалуйста, ознакомьтесь с нашей политикой конфиденциальности, в которой говорится о том, как мы защищаем и управляем вашими данными.