| Maximum output: | 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m] |
| Nominal output: | 110dB(A) @ 1m +/- 3dB – Tone 2 [101dB(A) @ 10ft/3m] |
| No. of tones: | 32 (UKOOA / PFEER compliant) |
| Volume control: | Max. 110dB(A); Min. 72dB(A) – Tone 2 |
| Effective range: | 100m/328ft @ 1KHz |
| Voltages DC: | 12vdc; 24vdc; 48vdc |
| Voltages AC: | 115vac; 230vac |
| Energy: | 5 Joules (5Ws) |
| Flash rate: | 1Hz (60 fpm) |
| Peak Candela: | 500,000 cd – calculated from energy (J) 39,463 cd* – measured ref. to I.E.S. |
| Eff. Intensity: | 250 cd – calculated from energy (J) 120 cd* – measured ref. to I.E.S. |
| Lens colours: | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
| Tube life : | Emissions are reduced to 70% after 5 million flashes |
| Ingress protection: | IP66/67 |
| Enclosure matl: | Marine grade copper free LM6 Aluminium |
| Enclosure finish: | Chromate & powder coated |
| Horn material: | High impact UL94 V0 & 5VA FR ABS (Red) |
| Cable entries: | Dual M20 ISO (one stopping plug included) |
| Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
| Enclosure volume: | <2 litres |
| Grounding stud: | M5 |
| Temperature range: | -50° to +70°C (-58°F to +158°F) |
| Relative humidity: | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
| MTBF AC: | 66.56 years / 583,091 hours – MIL217 |
| Weight: | DC: 4.80kg/10.56Ibs AC: 5.00kg/11Ibs |
| Note | SPL data +/-3dB(A), Candela with clear lens – at optimum voltage |
| Part Code: | Identifier: | Description: |
|---|---|---|
| Product type: | BExCTS11005 | Explosion proof Telephone Initiated Alarm Horn Sounder & 5J Xenon Beacon |
| Type: | DPF | Ex d, UV stable PC Colour Lens, Flare Horn |
| Voltage: | DC012 DC024 DC048 AC115 AC230 | 12V dc 24V dc 48V dc 115V ac 240V ac |
| Cable entries:[e] | A B C D E F G | 2 x M20x1.5mm 2 × 1/2" NPT – adaptors 2 × 3/4" NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 1/2" NPT – adaptor 1 × 3/4" NPT – adaptor 1 x M25x1.5mm – adaptor |
| Stopping plug/adaptor material: [m] | B N S | Brass Nickel Plated Stainless Steel |
| Bracket/Guard matl & tag: [s] | 1 2 3 4 | A2 304 Stainless Steel A4 316 Stainless Steel A2 304 St/St with Equip. Tag A4 316 St/St with Equip. Tag |
| Product version: [v] | A1 | Default – IECEx, ATEX, Ex EAC & INMETRO |
| Enclosure colour: [x] | R S | Red Special – contact E2S |
| Lens colour: [y] | A B C G M R Y | Amber Blue Clear Green Magenta Red Yellow |
| Accessories: | SP65-0001-A4 SP65-0003-A4 | Pole Mount Bracket Kit St/St A4 (316) Sunshade – St/St A4 (316) |
| Version: | Voltage: | Current: | Voltage: | Current: |
|---|---|---|---|---|
| Alarm Sounder | Xenon Beacon | |||
| 12V dc | +/-25% | 195mA | 10-14V | 750mA |
| 24V dc | +/-25% | 265mA | 20-28V | 300mA |
| 48V dc | +/-25% | 130mA | 42-54V | 180mA |
| 115V ac | 50/60Hz | +/-10% | 110mA+/-10% | 140mA |
| 230V ac | 50/60Hz | +/-10% | 56mA+/-10% | 55mA |
| Amber | Blue | Clear | Green | Red | Yellow |
| 0.70 | 0.24 | 1.00 | 0.25 | 0.23 | 0.93 |