D2xC1X05 Alarm Horn Sounder & Xenon Strobe 5J Horn 116dB(A) and 5J Xenon

Features and Functions

  • 5 Joule Xenon beacon with 116dB(A) alarm horn
  • UL464/UL1638 Fire Alarm
  • Effective Intensity: 94.78 cd
  • Peak Candela: 33,410 cd
  • 64 alarm tones, 4 remotely selectable alarm stages/channels
  • Field replaceable lens colour filters
  • Dual cable entries
  • Supplied with haz loc rated stopping plugs/adaptors
Ul badge certified
Ul
Iecex approval
Atex approval
Csfm
Ex eac logo
Eac logo
Ce approval
Ukca

Overview

The corrosion proof, marine grade aluminium die cast enclosure is chromated and powder coated providing resilience in the harshest of hazardous location environments. One device, globally certified: ATEX, IECEx Zone 2 & 22; NEC/CEC CI D2 and CII D2; NEC CI Zone 2 and Zone 22; CEC Zone 2 & 22 and CII D2. UL & cUL approved 24Vdc version for fire alarm use.
Downloads
Datasheet Download
Installation Manual Download
IECEx certificate Download
ATEX certificate Download
UL certificate of compliance Download
CSFM Listing Download
UKCA Certificate Download
ECAS Ex Approval Download
Declaration of Conformity Download
Declaration of Conformity UKCA Download
2D drawing (PDF) Download
2D drawing (DWG) Download
3D drawing (STEP) Download
Wiring Schematic Download
Nameplate Drawing Download
Equipment Tag Drawing Download
Duty Label Drawing Download
Pole Mount & Sun Shade Drawing Download
Hi-res product image 1 (TIFF) Download
Hi-res product image 2 (TIFF) Download
Hi-res product image 3 (TIFF) Download
Specification
Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output: 112dB(A) @ 1m +/- 3dB – Tone 2 [103dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A) [Tone 2]
Effective range: 125m/410ft @ 1KHz
Stage switching: DC units – Positive or Negative line.
AC units – common supply line
Energy: 5 Joules (5Ws)
Flash rate: 1Hz (60 fpm)
Peak Candela: 500,000 cd – calculated from energy (J)
33,410 cd – measured ref. to I.E.S.
Effective Intensity cd: 250 cd – calculated from energy (J)
Effective Intensity: 94.78 cd – measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Tube life: Emissions are reduced to 70% after 8 million flashes
Voltages DC: 24V dc [20-28Vdc]; 48V dc [38-58Vdc]
In rush: 2.2A for <9ms
Voltages AC: 115V ac 50/60Hz; 230V ac 50/60Hz
Ingress protection: EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure material: Marine grade aluminium LM6
Enclosure finish: Chromate & powder coated finish
ISO 12944-6 CX, C5VH & C5H
Enclosure colour: Red or Grey, custom colours available on request
Cable entries: 2 x M20 x 1.5mm threaded gland entries
Adaptors available to 1/2"NPT, 3/4"NPT and M25
Terminals: 0.5 – 2.5mm² (20-14 AWG)
Grounding stud: M5
Operating temp: -40 to +70°C [-40° to +158°F] – Class I Div 2
-40 to +50°C [-40° to +122°F] – All other approvals
Relative humidity: 99% – tropicalised/conformal coated electronics
Weight: DC: 2.80kg/6.16Ibs AC:3.10kg/6.82Ibs
Part codes
Part Code:Identifier:Description:
Product type:D2xC1X05Haz Loc alarm horn sounder & Xenon strobe warning light / beacon
Voltage:DC024
DC048
AC115
AC230
24V dc – UL/cUL Fire Alarm
48V dc
115V ac
230V ac
Cable Entry Type:[e]A
B
C
D
E
F
G
2 x M20x1.5mm
2 × 1/2" NPT – adaptors
2 × 3/4" NPT – adaptors
2 x M25x1.5mm – adaptors
1 × 1/2" NPT – adaptor
1 × 3/4" NPT – adaptor
1 x M25x1.5mm – adaptor
Stopping plug/ adaptor material: [m]N
S
Nickel Plated
Stainless Steel
Guard material & tag: [s]1
3
5
A4 316 Stainless Steel
A4 316 St/St with Equip. Tag
A4 316 St/St with Equip. Tag & Duty Label
Product version: [v]AUL, cUL, IECEx, ATEX, CSFM, Ex EAC
Product option:[o]1
X
Standard product
Custom configuration – contact E2S
Enclosure colour: [x]R
G
S
Red
Grey
Special colour – contact E2S
Lens colour: [y]A
B
C
G
M
R
Y
Amber
Blue
Clear
Green
Magenta
Red
Yellow
Accessories
SP65-0001-A4
SP65-0003-A4
Current Consumption
Product Version:Nominal Voltage:Voltage Range:Current Consumption:
DC02424V dc10-30V dc313mA [at nominal voltage]
DC04848V dc38-58V dc181mA [at nominal voltage]
AC115115V ac 50/60Hz+/-10%89mA
AC230230V ac 50/60Hz+/-10%52mA
DC02424V dc20-28V dc275mA [at nominal voltage]
DC04848V dc42-54V dc145mA [at nominal voltage]
AC115115V ac 50/60Hz+/-10%80mA
AC230230V ac 50/60Hz+/-10%30mA
DC02424V dc20-28V dc513mA [at nominal voltage]
DC04848V dc42-54V dc311mA [at nominal voltage]
AC115115V ac 50/60Hz+/-10%174mA
AC230230V ac 50/60Hz+/-10%63mA
Approvals
  • UL File ref: E230764
  • IECEx cert: IECEx ULD 14.0004X
  • ATEX cert: DEMKO 14 ATEX 4786493904X
  • CSFM listing: 7136-2279:0503
  • Ex EAC certified: EAC RU C GB.AA71.B.00273/20
Coding
  • NEC / CEC:
    Class I Div 2 ABCD T2B Ta -40°C to +70°C
    Class I Div 2 ABCD T2C Ta -40°C to +55°C
    Class I Div 2 ABCD T2D Ta -40°C to +40°C
    Class II Div 2 FG T5 Ta -40°C to +50°C
    Class III Div 1&2 Ta -40°C to +50°C
  • NEC:
    Class I Zone 2 AEx ec IIC T2 Gc Ta -40ºC to +50°C
    Zone 22 AEx tc IIIC T120°C Dc Ta -40ºC to +50°C
  • CEC:
    Class I Zone 2 Ex ec IIC T2B Gc X Ta -40ºC to +50°C
    Class I Zone 2 Ex ec IIC T2C Gc X Ta -40ºC to +45°C
    Zone 22 Ex tc IIIC T120°C Dc Ta -40ºC to +50°C
  • IECEx & ATEX:
    II 3G Ex ec IIC T2 Gc Ta -40ºC to +50°C
    II 3D Ex tc IIIC T90ºC Dc Ta -40ºC to +50°C
    See product manual for full voltage specific coding.
Effective Candela lens colour factor
AmberBlueClearGreenMagentaRedYellow
0.590.271.000.510.340.150.85
Tone Table
Stage 1 WAV file Frequency Description. Stage 2 Stage 3
T 1 T 3 T 2
T 2 T 1 T 3
T 3 T 1 T 2
T 4 T 44 T 24
T 5 T 52 T 19
T 6 T 7 T 44
T 7 T 6 T 44
T 8 T 44 T 24
T 9 T 18 T 34
T 10 T 21 T 34
T 11 T 44 T 1
T 12 T 44 T 1
T 13 T 44 T 1
T 14 T 23 T 3
T 15 T 44 T 24
T 16 T 44 T 24
T 17 T 44 T 24
T 18 T 44 T 24
T 19 T 64 T 24
T 20 T 44 T 24
T 21 T 44 T 24
T 22 T 44 T 24
T 23 T 15 T 3
T 24 T 48 T 20
T 25 T 1 T 44
T 26 T 1 T 44
T 27 T 1 T 44
T 28 T 44 T 24
T 29 T 1 T 44
T 30 T 44 T 24
T 31 T 30 T 24
T 32 T 44 T 24
T 33 T 53 T 24
T 34 T 56 T 24
T 35 T 44 T 24
T 36 T 21 T 24
T 37 T 53 T 24
T 38 T 1 T 8
T 39 T 1 T 8
T 40 T 44 T 24
T 41 T 1 T 8
T 42 T 1 T 8
T 43 T 1 T 8
T 44 T 5 T 24
T 45 T 1 T 8
T 46 T 53 T 24
T 47 T 57 T 24
T 48 T 44 T 24
T 49 T 44 T 24
T 50 T 44 T 24
T 51 T 44 T 24
T 52 T 64 T 24
T 53 T 56 T 24
T 54 T 57 T 24
T 55 T 54 T 24
T 56 T 57 T 24
T 57 T 47 T 24
T 58 T 54 T 24
T 59 T 44 T 24
T 60 T 44 T 24
T 61 T 44 T 24
T 62 T 44 T 24
T 63 T 44 T 24
T 64 T 44 T 21

Настройки файлов cookie

Мы используем файлы cookie, чтобы обеспечить вам удобство прохождения собеседований, улучшить наш продукт, персонализировать ваш опыт и поддержать наши маркетинговые усилия. Полный список файлов cookie, используемых по категориям, приведен ниже. Вы можете отказаться/отключиться в любое время. Для получения более подробной информации ознакомьтесь с нашей полной политикой конфиденциальности.

Строго необходимые файлы cookie
Эти файлы cookie необходимы для работы нашего веб-сайта и не могут быть отключены. К ним относятся файлы cookie, используемые для аутентификации и статуса, безопасности, персонализации и функций корзины покупок.
Файлы cookie производительности и аналитики
Эти файлы cookie позволяют нам измерять посещаемость веб-сайта и источники трафика. Мы используем их для определения популярных страниц и оптимизации работы сайта.
Целевые файлы cookie
Эти файлы cookie позволяют нам измерять эффективность нашей маркетинговой программы и устанавливаются нашими рекламными партнерами. Их можно использовать для создания профиля ваших интересов и для показа соответствующей рекламы на других веб-сайтах.

Получить типовой расчет

Предоставьте свои контактные данные, и мы скоро свяжемся с вами!
В этой форме указывается ваше имя и контактная информация. Пожалуйста, ознакомьтесь с нашей политикой конфиденциальности, в которой говорится о том, как мы защищаем и управляем вашими данными.